FICL II Interface

FICL was developed to provide a platform and operating system independent control method for the extensive range of Kemo electronic filters.
The system is based on the IEE 488.2 protocol and uses simple ASCII text commands. Instruments can be interrogated to confirm their settings, very important for 'traceability' of measurements. Similar commands are used across the Kemo filter range.
FICLII is an updated version of FICL. Running with TCIP ,Ethernet hardware, RJ45 plugs. It features, simplified operation, faster responses, greater control over each filter system, and all round easier to use.
The use of Ethernet hardware and simple ASCII text commands make FICL II easy to interface into complex measurement systems.
FICL II can address 64 channel addresses, however more than one channel can share a FICL II channel address. Therefore if a group of channels are always going to be used with the same settings, they can be set to the same channel address, and one single command will set all these channels simultaneously.
FICL II gives direct control of the filter system settings, it does not interpret, it does what you command it to do.

Typical commands are:-

FREQ,1,250

This sets frequency of channel 1 to frequency step 250

IGNA,5,2

This sets input gain section A of channel 5 to gain value 2

ICPL,6,dc

This sets the input coupling of channel 6 to DC coupling.

RDBK,1
CM255G at address 1
IGNA,1
IGNB,1
ICPL,AC
IMOD,SE
IEPE,0
FREQ,27
CM255G ready

The above listing shows the status of channel 1 of a CardMaster 255G system. All settings are listed with their current values.
RDBK,a would list the current status of all channels. The RDBK command also lists all available commands for a system.

FICL II is very easy to use and control, we use it every day in our technical centre to check and test filters.
Direct commands are easy to send using standard Windows 'HyperTerminal' which can be easily set to operate FICL.